GE KITZ 101/102 Interfaces

These flexible, secure KITZ interface units enableconversion between K-BUS ports and IEC60870 format data. Their robust andquality design makes them the ideal solution for use in multiple locations.

Flexible interfacing and conversion

KITZ provides conversion between K-BUS ports of IEC60870format data and an EIA232 serial connection via a Courier software package.Using a K-BUS system Courier Protocol enables communications with up to 32devices at a maximum distance of 1km in electronically hostile environments.

KITZ can also be used to directly interface with integratedSCADA (Supervisory Control and Data Acquisition) systems.

Simple connections for continuous communication

Designed to ensure local or remote connections with desktopand substation locations, KITZ can communicate with any K-BUS device.Manufactured to the same high standards as protection relays, KITZ providessimple EIA232 connections.

GE's transformer protection devices provide innovativesolutions for the protection, control and monitoring of transformer assets.Transformers have become an essential component for high voltage powertransmission, ensuring long distance transmission of power is economicallypractical. GE's transformer protection solutions enhance transformerreliability through special techniques and methods to increase the life oftransformers.

Application

The KITZ101/102 interface may be used to interface between 1and 32 Courier devices via:

PC serial port for local substation use:

 Compatible modems andtelephone networks for remote access

 RTU (Remote TerminalUnit) for integration in SCADA systems with Courier protocol capability

The KITZ101/102 converts K-Bus to IEC 60870 FT1.2 frameformat for use in computer based systems. It is typically applied insubstations where a number of compatible devices could be located, along withconnection equipment such as modems, RTU's or other SCADA equipment.

KITZ can provide local and remote access via K-Bus forsettings changes, disturbance and event record extraction and also for circuitbreaker operations.

KITZ101/102 may be integrated into intelligent SCADA systemswhere all or part of the system is available on the Courier protocol. Suchsystems simply require an EIA232 or fibre optic (via converters) port on theSCADA or RTU for connection to the KITZ101/102. SCADA systems without theCourier protocol may also utilise KITZ by use of other protocol converters, forexample KITZ202 for Modbus or KITZ204 for IEC 60870-5-103 based systems.