UDEY CTPTA-504 is a comprehensive CT and PT analyzer. It's constant voltage and current is highly stable. DSP system controls the constant voltage and current source output and amplitude. This source generates AC of 0-125V and or DC of 0-0.5A current to sample CT. The DSP system besides controlling the sources, also samples data and communicates with the internal computer. Display screen is large LCD with touch pad. The analyzer is highly accurate with high noise immunity and is very user friendly.

Machine Feature

Test standards : Ratio measurement : Built-in computer Large LCD display User interface Memory : Weight

Machine Technical Specification

Test Standards

IEC 60044-1, IEC 60044-2, IEC 60044-6

Power Output

0.1 to 180V (AC)

Current Output

0.001 to 5A (RMS)

Power Output

300VA

Test Frequency

: 0.1 to 60Hz

Maximum Knee Voltage Measurements

: 45KV

Current Measurement

Range: 0-10A (auto-range: 0.1A / 0.4A / 2A / 10A)
Error <± 0.1% RDG to 0.01%FS

Voltage Measurement

Range: 0-200V (auto-range: 1V / 10V / 70V / 200V)
Error <± 0.1% RDG to 0.01%FS

Turns Ratio Measurement

Range: 1 to 35000
:1-2000 error <0.05% RDG
:2000-5000 error < 0.1% RDG
5000-35000 error < 0.2% RDG

Phase Measurement

Error <± 2 min, resolution: 0.01 min

Coil Resistance Measurement

0 to 8 kohm (auto-range: 2 ohm/20 ohm/80 ohm/800 ohm/8 k ohm)
Error <± 0.2% RDG to 0.02% FS
:Maximum resolution: 0.1 Milli ohm

Temperature Measurement

-50 to 100°C, error: <3°C.

CT Secondary Burden

0 to 160 ohm (auto-range:2 ohm/20ohm/80ohm/160 ohm)
: Error <± 0.2% RDG to 0.02% FS
: Maximum Resolution: 0.001 ohm

PT Secondary Burden

0 to 80 kohm (auto-range: 800 ohm/8 k ohm / 80 kohm)
: Error <± 0.2% RDG to 0.02% FS
: Maximum Resolution: 0.1 ohm

PT Ratio Measurement

Range: 1 to 35000
: 1-5000 error < 0.2%
: 5000-35000 error < 0.5%

PT Phase Angle Measurement Error

< 30 min

Saved Data Groups

> 1000 groups

Power Supply

AC 220V ± 10%, 50Hz / 60 Hz

Dimensions

485mm x 356mm x 183mm approximate

Weight

< 13 Kg approximate